• Technical Data
    Design

    Comfort control system for all conventional pumps in glandless and glanded design with fixed speeds and three-phase motors.

     

    Application

    For continuous power adjustment to the variable operating states of single-, dual- or multi-pump systems (up to 6 pumps). Controlling depends on the differential pressure Δp, feed/return temperature (±T) or differential temperature (ΔT), including the free adjustment of the duty point by means of advance correction of the full-load pump output.

     

    Equipment/function

    How it works

    Wilo Comfort Control Systems enable the infinitely variable electronically controlled power adjustment of pumps to the variable operating statuses of the hydraulic system, depending on the pressure (p), volume flow (Q) and temperature (T) control variables.

    Equipment features

    • PID controller
    • Integrated real time clock with summer/winter time switchover
    • Integrated individual/total elapsed time indicator
    • Service life optimisation for multi-pump systems
    • Motor protection by connection of WSK, PTC TS and TSA
    • Multi-colour touch display with backlight
    • Status display for drives (e.g. pumps and frequency converters)
    • User-oriented menu navigation with multi-language plain text display and/or symbol navigation
    • Storage and display of extensive operating data
    • Defined display of error messages and storage in the history memory
    • Wire break monitoring of the transmitter paths

     

    Technical data
    • Device versions
      • Wall fixation (WM) up to P2 = 4 kW
      • Floor model (BM) from P2 = 5.5 kW
      • Version for control panel installation on request
    • Protection class IP54
    • Mains connection 3~400 V, 50 Hz
    • for pumps with a rated power of P2 = 1.1 to 45 kW (higher power and other voltages on request)
    • Speed control range of 100 % and 30 % of the rated motor speed
    • Power factor cos φ of > 0.90
    • Efficiency at Pmax of > 0.93 and within the permissible partial load range of > 0.85
    • Output voltage of 3 x 130 V – 400 V
    • Output frequency of (10 Hz) 12 Hz – 50/60 Hz
    • Permitted ambient temperature 0 °C to +40 °C

Why Wilo Pumps…

test

Self-Priming

test

Convenient

test

Highly-Efficient

test

Noise-Free

test

Diversity

test

Optimised Design

What Trebles Customers Think

We relied on Trebles expertise to ensure the right products were sourced for our project.

Top workmanship and a professional attitude from a supportive team

Excellent customer service again! You genuinely make my life so much easier