Advantages
- Reliable control and monitoring of up to four pumps, thanks to various monitoring and alarm functions
- Flexible level measurement with level sensor or float switches
- Additional operational safety thanks to separate level recording for high water and dry-running protection
- Easy operation with alphanumeric, symbol-based menu and operating button
- Transparent indication of operating status thanks to a clear and manageable display
- Universal use for water supply and sewage disposal – also for pumps in potentially explosive atmospheres
- Optional versions available:
- Direct connection (without accessories) of pumps and level sensors within potentially explosive atmospheres
- Extensions for convenient integration into remote monitoring systems via BACnet, Modbus, LON or GSM
-
Technical Data
Design
Microprocessor-controlled switchgear for level-dependent control of up to four submersible pumps.
Equipment/function
Functions
- Three different operating modes for a broad field of application:
- “Drain” operating mode: For draining sewage chambers
- “Fill” operating mode: For filling water tanks and rainwater storage tanks
- “FTS” operating mode: For controlling solids separation systems
- Configurable overload protection
- Thermal motor monitoring
- Pump kick function
- Adjustable follow-up time
- Automatic pump cycling (from 2 pumps)
- Service life optimisation (from 2 pumps)
- Standby pump (from 2 pumps)
- Fault-actuated switchover (from 2 pumps)
- Direction of rotation monitoring
- High water alarm with forced switch-on of the connected pump(s)
- Dry-running protection
- Fault memory for 16 error messages including the type of fault
- Maintenance monitoring
Equipment
- Max. number of connectable pumps: max. 2 pumps with float switch, max. 4 pumps with level sensor
- Display of the current operating status and data, as well as faults, using the LCD display and LEDs
- Elapsed time indicator
- Symbol-based menu navigation
- Configuration of operating parameters and operation via operating button
- Main switch
- Motor protection switch in the “DOL” version
- Fuse and motor protection relay in the “SD” version
- Operating mode selection switch per pump: Emergency/test mode, off, automatic mode
- Remote access via Modbus RTU, BACnet and optionally GSM.
Typekey
Example: Wilo-Control SC-L 2x18A-T4-SD-WM-Ex Control Switchgear SC Smart Control series L “Lift” version for water lifting applications 2 Number of pumps that can be connected 18A Maximum rated current per pump T4 Mains connection: M = 1~220–230 V, 50/60 Hz
T4 = 3~380–400 V, 50/60 Hz
34 = line voltage, e.g. 380 – 400 V
SD Starting mode of the connected pumps: - DOL = direct starting (direct on line)
- SD = star-delta starting
WM Installation type: Wall installation Ex Version for direct connection of Ex-approved pumps Technical data
- Mains connection: 1~230 V, 50/60 Hz or 3~ 380/400 V, 50/60 Hz or according to customer request
- Max. rated power (P2) per pump:
- 15 kW with direct starting
- 37 kW with star-delta starting
- Maximum rated current IN per pump:
- 32 A with direct starting
- 72 A with star-delta starting
- Activation type: Direct or star-delta
- Control voltage: 24 VDC, 230 VAC
- Operating temperature: 0…+40 °C
- Storage temperature: -10…+50 °C
- Max. relative humidity: 50 %
- Housing material: Coated steel sheeting
- Protection class: IP54
- Electrical safety: Pollution degree II
Construction
Microprocessor-controlled switchgear for level-dependent control of 1 … 4 submersible pumps with analogue or digital signal transmitters. Individual parameters are entered via symbol-based menu navigation and an operating button.
Inputs
1x analogue precision input 4 – 20 mA for level control with level sensor
2x (for 1 pump) or 3x (for 2 pumps) digital inputs for level control with float switch
1x digital input for low water level with float switch (dry-running protection)
1x digital input for high water signal with float switch (high water alarm)
1x input per connected pump for thermal winding monitoring for bimetal or PTC temperature sensor
1x input per connected pump for connecting moisture sensors (e.g.: motor compartment leakage or sealing chamber monitoring)
1x digital input for External On/Off for remote activation and deactivation of automatic mode
Outputs
1x potential-free contact for the collective run signal (SBM)
1x potential-free contact for the collective fault signal (SSM)
1x potential-free contact for the high water alarm
1x potential-free contact as a signal to start a pump-dependent submersible mixer (when idle)
1x analogue output 0-10 V for the output of the actual level value
Configuration
Caution! Signal transmitters are to be provided on-site. Switchgears are not protected against explosions and may only be used outside potentially explosive atmospheres. Signal transmitters within potentially explosive atmospheres must be connected through an intrinsically safe circuit, e.g. breakdown barrier or Ex cut-off relay.
The direct connection of pumps and/or signal transmitters within potentially explosive atmospheres is only possible with the “Ex” version of the switchgear!
- Three different operating modes for a broad field of application: