Description
Vessels to protect Flexcon expansion vessels on elevated temperature systems or reduce the on/of cycling of the heat pump.
The vessels are fitted in between the expansion vessel and the system return.
System water flows from the installation into the top of the vessel. From the bottom of the vessel, significantly cooler water is fed into the expansion vessel. -
Technical Features
Maximum working pressure: 10.0 bar.
Minimum / Maximum operating temperature: -10 / 95 °C.
Suitable for addition of glycol-based anti-freeze up to 50%.
Red (RAL 3002) epoxy powder coating.
This vessel is manufactured in accordance with sound engineering practice and satisfies the essential design requirements of the member state. -