Description
Execution
Energy saving variable speed circulating pump driven by a permanent magnet synchronous motor (pm) controlled by on board inverter.
Bronze pump casing.Applications
Sanitary hot water systems.
Operating conditions
Liquid temperature from +2 °C to +95 °C
Ambient temperature from +2 °C to +40 °C
– Maximum permissible working pressure: 10 bar
– Storage: -20°C/+70°C max. relative humidity 95% at 40 °C
– Certifications: in conformity with CE requirements
Sound pressure ≤ 43 dB (A).
Pressione minima in aspirazione: 0,3 bar a 50 °C, 1,0 bar a 95 °C
EMC secondo: EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3.
Threated ports ISO 228: G 1, G 1 1/4, G 1 1/2. -
Technical Features
Technical data
FLOW
0.1 / 3.3
mc / hHEAD
0.2 / 3.8
mPOWER
0.0045 / 0.044
kW - Downloads