Wilo-Stratos GIGA B

Maximum performance at the highest levels of energy efficiency.

Enquire About This Product

  • Description

    The Wilo-Stratos GIGA B is the ideal high-efficiency pump for use in heating, air conditioning and cooling applications in buildings where large volumes of water have to be pumped to great delivery heads.

  • Advantages
    • Innovative, high-efficiency pump for maximum overall efficiency with principal dimensions in accordance with EN 733
    • High-efficiency EC motor with efficiency class IE5 in accordance with IEC 60034-30-2
    • Integrated pump support feet and optional supporting block allow for easy installation
    • Optional interfaces for bus communication using plug-in IF-Modules
  • Technical Features

    Design

    High-efficiency monobloc pump with IE5 motor and electronic power adjustment in glanded pump design. Version as single-stage low-pressure centrifugal pump with flange connection and mechanical seal.

     

    Application
    • The pumping of heating water (in accordance with VDI 2035), chilled water and water-glycol mixtures without abrasive substances in heating, chilled water and cooling systems.

       

    Typekey

    Example Wilo-Stratos GIGA B 40/1-51/4.5
    Stratos GIGA High-efficiency pump
    B Monobloc design
    40 Nominal diameter DN of the flange connection (for Stratos GIGA B: discharge side) [mm]
    1-51 1 = lowest selectable delivery head [m] 51 = highest selectable delivery head [m]
    4.5 Rated power P2 in [kW]
    -xx Version: E.g. R1 – version without differential pressure sensor

     

    Technical data

      • Permitted temperature range of the fluid: -20 °C to +140 °C
      • Mechanical seal for pumping water up to Tmax = +140 °C. Up to T ≤ +40 °C, a glycol admixture of 20 % to 40 % by volume is permissible. An alternative mechanical seal must be provided for water-glycol mixtures with a glycol content of > 40% to max. 50% by volume and a fluid temperature of > +40 °C to max. +120 °C or other fluids that differ from water. When using water-glycol mixtures, the use of an S1 variant with a corresponding mechanical seal is generally recommended.
      • Mains connection:
      • 3~440 V ±10 %, 50/60 Hz
      • 3~400 V ±10 %, 50/60 Hz
      • 3~380 V -5% +10%, 50/60 Hz

      Compliance with electromagnetic compatibility without additional measures:

        • Interference emission for residential environment according to EN 61800-3:2018
        • Interference immunity for industrial environments according to EN 61800-3:2018
      • Protection class IP55
      • Max. operating pressure 16 bar up to +120 °C, 13 bar up to +140 °C

     

    Equipment/function

    Operating modes

    • Δp-c for constant differential pressure
    • Δp-v for variable differential pressure
    • PID-Control
    • Constant speed (n=constant)

     

    Manual operation level

    • Green button and display

     

    Manual functions

    • Differential pressure setpoint setting
    • Setting the speed (manual control mode)
    • Setting the operating mode
    • Setting the pump ON/OFF
    • Configuration of all operating parameters
    • Fault acknowledgement

     

    External control functions

    • “Overriding Off” control input
    • “External pump cycling” control input (only effective in twin-head pump operation)
    • Analogue input 0 – 10 V, 0 – 20 mA for constant speed (DDC) and remote setpoint adjustment
    • Analogue input 2 – 10 V, 4 – 20 mA for constant speed (DDC) and remote setpoint adjustment
    • Analogue input 0 – 10 V for actual value signal from pressure sensor
    • Analogue input 2 – 10 V, 0 – 20 mA, 4 – 20 mA for actual value signal from pressure sensor

     

    Signal and display functions

    • Collective fault signal SSM
    • Collective run signal SBM

     

    Data exchange

    • Infrared interface for wireless data exchange with IR-Monitor/IR-Stick
    • Plug-in position for Wilo IF-Modules (Modbus, BACnet, CAN, PLR, LON) for connection to building automation

     

    Safety functions

    • Full motor protection with integrated trip electronics
    • Access disable

     

    Dual pump management (2 x single pump, Y-piece application only)

    • Main/standby operation (automatic fault-actuated switchover)
    • Pump cycling main/standby operation after 24 hours
    • Parallel operation

     

    Accessories

    • 1 mounting bracket with fixation material for installation on a base
    • Installation aid for mechanical seal
    • IR-Stick
    • IF module PLR for connecting to PLR/interface converter
    • IF module LON for connection to the LONWORKS network
    • IF module BACnet
    • IF module Modbus
    • IF module CAN
    • Control system VR-HVAC
    • Control system CCe-HVAC
    • Control system SCe-HVAC
    • Differential pressure sensor kits 0 – 10 V for pumps in version …-R1

     

    Option

    • Variant …-R1 without differential pressure sensor
    • …-S1 variant with special mechanical seal

     

    Materials

    • Pump housing and lantern: EN-GJL-250
    • Impeller: PPS-GF40
    • Shaft: 1.4122
    • Mechanical seal: AQEGG; other mechanical seals on request
  • Downloads

Why Wilo Pumps…

test

Self-Priming

test

Convenient

test

Highly-Efficient

test

Noise-Free

test

Diversity

test

Optimised Design

What Trebles Customers Think

We relied on Trebles expertise to ensure the right products were sourced for our project.

Top workmanship and a professional attitude from a supportive team

Excellent customer service again! You genuinely make my life so much easier

Excellent service and a company I would recommend to anyone in future

Engineers were very professional with an excellent knowledge of their trade

We’re writing to express our sincere thanks to all who help ensure our hospitals are able to run smoothly

Job delivered and commissioned at the height of the pandemic with no changes to the excellent service we always receive.

The team at Trebles were great. I really can’t praise them enough.

Not many providers would be able to fully breakdown & rebuild a booster on site