Description
Compact and fully-automatic sewage lifting unit for above-ground and concealed floor installation within buildings.
-
Advantages
- Easy to install due to integrated pump and non-return valve
- The large tank volume ensures a low number of switching processes
- Easy maintenance
- Stainless steel tile frame with trap
-
Technical Features
Design
Compact and fully-automatic sewage lifting unit for above-ground and concealed floor installation within buildings.
Application
- As a lifting unit within buildings (floor-mounted installation)
- As a pump chamber within buildings (concealed floor installation)
- For backflow resistant drainage of
- Drainage points below the backflow level
- Drainage points that cannot be drained via the natural downward slope.
Liquid
For collection and pumping of the following in domestic areas:
- Sewage not containing faeces
Sewage pumping according to 12050
The pumps meet the requirements of EN 12050-2.
Equipment/function
- DrainLift BOX …
- Submersible pump with thermal motor monitoring
- Fitted float switch
- Ready-to-plug
DrainLift BOX … D
- Submersible pump with thermal motor monitoring
- Fitted float switch
- Ready-to-plug
DrainLift BOX … DS
- Submersible pump with thermal motor monitoring
- Separate float switch in pump chamber
- Switchgear with mains-independent alarm and collective fault signal
Typekey
Example: Wilo-DrainLift BOX-32/11HD DS O BOX Sewage lifting unit for sewage free of faeces 32 Nominal diameter discharge connection of the installed pump 11 Max. delivery head in m HD HD = Pump for aggressive fluids D Lifting unit version: - E = Single-pump system
- D = Double-pump system
S Pump control: - Without = Pump with float switch
- S = Switchgear with float switch
O Installation type: - O = Floor-mounted installation
- U = Concealed floor installation
Technical Data
- Mains connection: 1~230 V, 50 Hz
- Discharge connection: 40 mm
- Inlet connection: 110 mm (DN 100)
- Ventilation connection: 110 mm (DN 100)
- Tank volume: 113 l
- Switching volume: 22 … 30 l
- Switchgear protection class (for DS version): IP54
Materials
- DrainLift BOX-32 …
- Pump chamber:
- Tank: PE
- Pipework: PE
- Non-return valve: PE
- Pump:
- Pump housing: PP-GF30
- Motor housing: 1.4301 (AISI 304)HD version: AISI 316L
- Impeller: PPE/PS-GF20
- Seal on the motor side: NBR
- Seal on the fluid side: C/SIC (BQ1PFF)
- Static seal: NBR
DrainLift BOX-40 …
- Pump chamber:
- Tank: PE
- Pipework: PE
- Non-return valve: PE
- Pump:
- Pump housing: EN-GJL-200 (ASTM A48 Class 30)
- Motor housing: 1.4301 (AISI 304)
- Impeller: PK-GF30
- Seal on the motor side: NBR
- Seal on the fluid side: C/MgSi (BXPFF)
- Static seal: NBR
- Pump chamber:
Accessories
- Collar − to stop ground water from seeping into the concealed floor installation.
- Alarm switchgears − to detect leakages.
- Float switch − to detect high water levels.
- Diaphragm pump − for emergency draining.
- Stop valve
-
Downloads
Click Below to Download:
Wilo-DrainLift BOX
Wilo-DrainLift Box Certification Booklet
Group Statement REACH