CP2, CP2-G / DCP2, DCP2-G by DAB are in-line pumps designed for conditioning, heating and water recirculation in the presence of thermal solar panels (solar collectors) in commercial building service. The pump body and the motor support are in cast iron, the impeller is in cast iron or technopolymer depending on the model. In-line flanged ports. CP-G models equipped with coupling. The CP2 and CP2-G are single pumps, the DCP2 and DCP2-G are twin pumps. All models have a two-pole motor.
Flow rate (range) Up to 36 m3 Head Up to 50 m Type of pumped liquid Clean, free from solid or abrasive substances, non-viscous, non-aggressive, non-crystallized Glycol percentage (maximum) 50% Liquid temperature (range) -15°C + 140°C Maximum room temperature +50°C Operation pressure (maximum) 16 bar Flanging or threading Flange PN10/PN16 Motor efficiency class IE2 up to 0,55 kW; IE3 ≥ 0,75 kW Motor protection class IP 55 Motor insulation class F Impeller material Cast iron or technopolymer Three phase power input 3×230 V 50 Hz / 3×400 V 50 Hz 2910 rpm Type of installation Fixed horizontally or vertically as long as the motor is positioned above the pump.
For powers above 7.5 kW vertical installation only. - Downloads